Corrections to: TSI.STANDARD V4.2 (b)

DDC02.04 - ENV: Level of site risks at individual sites

Each data centre must fulfil all other criteria at a minimum level, with the exception of a maximum of one criterion.

B: The minimum level per site is level 2.
C: The minimum level per site is level 3.

This criterion does not apply to dual-site level 2. The "B" in DDC Level2 was set incorrectly.

DDC08.01 - POW: Target level achievement of individual data centers

Depending on the dual site target level, each data centre fulfils a minimum level in the POW area.

A: Each data centre fulfils at least individual level 1. The power supply to the data centres is independent of each other.

B: Each data centre fulfils at least single level 2.

C: Each data centre fulfils at least individual level 3.

The information on exposure class A was incomplete.